0.05% Single Phase Reference Standard Meter

0.05% Single Phase Reference Standard Meter

ブランド名: GENY
モデル番号: SZ-03A-K6
MOQ: 1個
価格: 交渉可能
支払条件: L/C、T/T、D/P
供給能力: 100/年
詳細情報
起源の場所:
中国
証明:
ISO, CE
ドキュメント:
型番:
SZ01A-K3
試験電圧範囲:
30V 480V
電圧供給:
220V ± 10%,50/60Hz ± 2Hz
周囲温度:
10°Cから30°C
尺寸 (W×H×D) (mm):
325×109×288
相対湿度:
45% - 75%
パッケージの詳細:
アルミケースと紙箱
供給の能力:
100/年
ハイライト:

single phase reference standard meter

,

0.05% accuracy reference standard

,

stationary electrical reference meter

製品の説明
0.05% Single Phase Reference Standard Meter
Product Overview
The Stationary Reference Standard from Guangzhou GENY Electric Co., Ltd is a high-precision Single Phase Reference Standard Meter designed for Stationary Single Phase Energy Meter Test Systems. With a wide current measurement range and accuracy up to 0.05%, this reference meter ensures reliable and stable performance for energy meter calibration, testing, and verification. It is widely used by utility companies, metrology laboratories, and energy meter manufacturers that require precise measurement and dependable testing equipment.
Key Features
  • High Accuracy up to 0.05% - Ideal for professional energy meter calibration and verification
  • Wide Current Measurement Range - Suitable for different testing requirements
  • Cost-Effective Solution - Excellent performance-to-price ratio for laboratories and manufacturers
  • Multiple Testing Modes - Supports active power and reactive power testing
  • Comprehensive Measurement Functions - Measures voltage, current, phase angle, frequency, power factor, active power, reactive power, and apparent power
  • RS232 Communication Interface - Measurement data can be easily managed and analyzed via computer
  • Stable and Reliable Performance - Designed for long-term stationary testing environments
Specifications
Model SZ01A-K3
Test Voltage Range 30V - 480V
Voltage Error ±0.05% (30V - 480V) ±0.1% (5V - 50V)
Voltage Display Range 5.000000V - 480.0000V
Test Current Range 10mA - 120A
Current Error ±0.05% (0.2A - 120A) ±0.1% (10mA - 0.2A)
Current Display Range 1.000000mA-120.0000A
Active Power Error ±0.05% (0.2A - 120A)
Reactive Power Error ±0.1% (0.2A - 120A)
Apparent Power Error ±0.1% (0.2A - 120A)
Phase Angle Range 0º - 360º
Phase Angle Error ±0.05º
Phase Angle Display Range 0.000001º - 359.9999º
Frequency Range 45Hz - 65Hz
Frequency Display Range 45.0000 - 65.0000
High Frequency Pulse Output 1*109 (0.2A - 1A) 1*108 (1A - 10A) 1*107 (10A - 120A)
Low Frequency Pulse Output 2*10-5*CH
Pulse Ratio 1:1
Output Level 5V
Voltage Supply 220V ± 10%, 50/60Hz ± 2Hz
Ambient Temperature 10°C - 30°C
Influence of External Fields ≤ 0.05% / mT
Relative Humidity 45% - 75%
Dimensions (W*H*D) 325*109*288 mm
Weight 5.5 kg
Applications
  • National Utility Companies - Energy meter verification and calibration
  • Government Metrology Institutes - Precision measurement and standard testing
  • Energy Meter Manufacturers - Production line testing and quality control
  • Power Laboratories and Calibration Centers
0.05% Single Phase Reference Standard Meter 0